Voltage drop calculator
Enter the current, the length and the cross-section of the cable, and we show the voltage drop in volts and percent, the smallest suitable cross-section and the loss.
Create a drawing Already have an account? Sign in
How do we calculate the voltage drop?
The calculator works for copper conductors at operating temperature, taking the resistance and reactance of the conductor (the full impedance) into account. On a single-phase network it takes the there-and-back path (two conductors), on a three-phase network the factor √3:
ΔU % = k · L · I · (R′ · cos φ + X′ · sin φ) / U · 100
where L is the one-way length of the cable in meters, I is the current, U is the nominal voltage (230 V or 400 V), and k is 2 for single-phase and √3 for three-phase. R′ = ρ / A is the resistance of the conductor per meter (the resistivity ρ of copper at operating temperature is 0.0225 Ω·mm²/m, and A is the cross-section in mm²), and X′ is the reactance per meter (0.08 mΩ/m). At cos φ = 1 the reactance term drops out. In the project sizing, L is the longest path from the board to the farthest device.
What does the result show?
- The voltage drop in percent and in volts.
- An indication of whether the value is within the selected limit: 3 % for lighting, 5 % for other circuits. A value between the two limits is a "borderline case": acceptable only for a non-lighting circuit.
- The smallest suitable cross-section from the sizes in the table, for the selected limit.
- The loss in the cable in watts.
What to watch out for
The calculator takes the cable length as one-way, so do not double it. Leave the power factor (cos φ) at 1 for resistive loads such as heating; enter a smaller value for motors and many kinds of electronics. This calculator does not check the current-carrying capacity of the cable: use the cable cross-section and MCB calculator for that.
Frequently asked questions
How large a voltage drop is allowed?
The calculator offers two limits: 3 % for lighting and 5 % for other circuits; these are the default values of the program's board rules. The actual requirement is set by the designer.
Do I have to enter the cable length there and back?
No. Enter the one-way length in meters; the calculation takes the there-and-back path into account itself.
Does it calculate for aluminum conductors too?
No, the calculator is for copper conductors.