NEC box fill calculator (314.16(B))
Enter the conductors, device yokes, grounding conductor and fittings of the box and we show the volume required by NEC 314.16(B) in in³, with the working line by line. If you enter the box volume, we also show whether they fit. An informative calculation; NEC mode is in beta.
Draw your plan Already have an account? Sign in
What does the box fill calculator compute?
According to NEC 314.16(B) it gives the volume (in³) a junction box needs for the conductors and devices, and, if you enter the box volume, whether they fit in it:
- Conductors: each takes the volume for its size (18 AWG 1.50 in³, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00 in³).
- Equipment grounding conductors: together they count as one conductor, by the largest size.
- Device yokes (switch or receptacle): each counts as two conductors.
- Internal cable clamps: together they count as one conductor.
- Fittings: together they count as one conductor, of the largest conductor size.
The result is shown line by line, so that it can be checked.
Worked example: switch box with two 14/2 cables and one switch
| Item | Volume |
|---|---|
| 4 current-carrying conductors, 14 AWG, 4 × 2.00 in³ | 8.00 in³ |
| Grounding conductors together, 14 AWG | 2.00 in³ |
| One switch (yoke), 2 × 2.00 in³ | 4.00 in³ |
| Total | 14.00 in³ |
This fits in an 18 in³ box and does not fit in a 10 in³ box.
What it does not compute
The calculator gives the conductor volumes of 314.16(B); you enter the box volume yourself (from the 314.16(A) table or the manufacturer's marking). It does not check other items in the box or special cases. It is an informative calculation, not a permit document: compliance is decided by the authority having jurisdiction (AHJ) and the NEC edition in force, and the values must be checked against the official text. The program's NEC mode is in beta.
Related calculator
To size the conduit for the conductors use the conduit fill calculator; for a whole plan see the US electrical plan page.
Frequently asked questions
How are the conductors counted?
Each conductor takes the volume for its size (per 314.16(B)), grounding conductors together count as one conductor, and each device yoke as two.
Where does the box volume come from?
You enter the box volume (from the 314.16(A) table or the manufacturer's marking); without it the calculator gives only the required volume.
Is this enough for a permit?
No. It is an informative calculation and NEC mode is in beta; compliance is decided by the authority having jurisdiction (AHJ) and the NEC edition in force, and the values must be checked against the official text.
Related pages
- NEC conduit fill calculator – fill of EMT and PVC conduits
- NEC load calculator – Article 220, standard and optional method
- US electrical plan (NEC) – the whole plan from the drawing
In detail in the tutorial
- Designing to the NEC (USA) – boxes and conduits per the NEC